Electrical |
 |
400 Amp service to demised premise at 120/208V, 3 Phase, 4 wire - (This amount subject to higher requirement due to if electrical heat over gas heat is used/added). |
 |
Flush mounted 42 circuit 400 amp panel including 200 amp breaker for additional sub panel. |
 |
Life safety and fire alarm system as required by code for all Landlord supplied items. |
Plumbing |
 |
1-1/2 inch copper water supply to demised premise (at minimum). |
 |
2-1/2 inch natural gas supply at minimum 1/4 psi. |
 |
4 inch sanitary sewer stubbed to premise at sufficient depth to accommodate all Tenant interior fixtures. |
 |
Appropriately sized grease interceptor as required by local codes. |
 |
Grease trap line run to space (tank requirements’ 1500 gallon minimum. |
 |
3 inch vertical plumbing vent stack and ability to vent directly to roof. |
Mechanical |
 |
HVAC equal to one ton per 150 square feet of premise. |
 |
Exhaust shaft to accommodate Type I Exhaust Hood. |
 |
Fresh air intakes for exhaust hood units (make up air) and a/c cooling units. |
 |
Sufficient rooftop space and structural capacity to accommodate Tenant's exhaust fans and make-up air units. |
 |
Telephone - 2" Conduit with Pull Rope Supplied to Leased Space. |